Enforcement standards
YD/T1173
Purpose
This cable is used in power transmission and distribution lines in mobile situations with a rated voltage of 0.6/1kV and below.
Usage Features
The long-term working temperature of the cable does not exceed 70°C. When short-circuited (the maximum time does not exceed 5s), the maximum temperature of the cable core does not exceed 160°C, the laying environment temperature is not lower than 0°C, and its minimum bending radius is not less than 6 times the outer diameter of the cable. times.
Models and specifications
Type number |
Name title |
Rated voltage V |
Core number |
Nominal cross-section mm2 |
RWZ
ZA-RVV ZA-RVV22
WDNA-RYY WDNA-RYY23 |
Flame-retardant plastic insulated flexible power cable |
600/1000 |
1-5 |
4.0-240 |
ZA-RV WDZA-RY |
450/750 |
1 |
1.5-500 |
Technical Performance
Nominal cross-section mm2 |
Conductor structure (number of wires/single wire nominal diameter) mm |
DC resistance at 20℃ ≤Ω/km |
44.0 |
56/0.30 |
4.95 |
6.0 |
84/0.30 |
3.30 |
10 |
77/0.40 |
1.91 |
16 |
126/0.40 |
1.21 |
25 |
196/0.40 |
0.780 |
35 |
266/0.40 |
0.554 |
50 |
380/0.40 |
0.386 |
70 |
523/0.40 |
0.272 |
95 |
741/0.40 |
0.206 |
120 |
902/0.40 |
0.161 |
150 |
1147/0.40 |
0.129 |
185 |
1406/0.40 |
0.106 |
240 |
1813/0.40 |
0.0801 |
300 |
2257/0.40 |
0.0641 |
Product Features
This product has flame retardant properties and uses a sheath material with high flame retardant properties, which greatly improves the flame retardant and fire-resistant properties of the cable. This product is suitable for places with high flame retardant requirements, such as high-rise buildings, subways, power stations, large industrial and mining enterprises and other places with high cable laying density and strict fire protection requirements. Compared with ordinary flame-retardant cables, this cable also has soft characteristics and a small bending radius, making it suitable for occasions with high bending and mobility requirements.
|